The Suppressed Voltage Rating (SVR)

Is a value that is assigned to an SPD by UL to indicate its protective characteristics.
Each mode of the SPD is subjected to three impulses of a 1.2/50μs, 6kV voltage waveform and a 8/20μs, 500A current waveform.
The “measured limiting voltage” is measured at the ends of 6” leads extending from the terminals of an OEM product or 6” extending from the enclosure of a wall-mounted SPD.
The average of these three measurements is then compared to the following chart and an SVR is assigned per each mode.


Average Measured
Limiting Voltage

Assigned SVR

330V or less

300V

331V ~ 400V

400V

401V ~ 500V

500V

501V ~ 600V

600V

601V ~ 700V

700V

701V ~ 800V

800V

801V ~ 900V

900V

901V ~ 1000V

1000V

1001V ~ 1200V

1200V

1201V ~ 1500V

1500V